工程術語庫 Engineering Glossary

系統邊界 system boundary
控制體積 control volume
累積 accumulation
交接 handoff
要求 requirement
假設 assumption
證據 evidence
偏差 deviation
型錄 product data sheet
查驗 verification
不確定度 uncertainty
冷媒 refrigerant
冷負荷 cooling load

維持室內條件所需移走熱量的速率。 Rate of heat removal required to maintain indoor conditions.

Q ≈ Qₛ + Qₗ

同時工況下比較房間與設備需要。 Compare room needs and equipment at coincident conditions.

得熱可能有時間延遲。 Heat gain can precede cooling load.

顯熱與潛熱 Sensible and Latent Heat

顯熱 sensible heat

與溫度改變有關的熱量。 Heat associated with a temperature change.

Qₛ ≈ ṁcₚΔT

用送風溫差估算顯熱處理量。 Estimate sensible air-side capacity from a supply temperature difference.

顯熱不等於總冷量。 Sensible capacity is only part of total capacity.

顯熱與潛熱 Sensible and Latent Heat

潛熱 latent heat

與相變或濕量移除有關的熱量。 Heat associated with phase change or moisture removal.

Qₗ ≈ ṁₐhfgΔw

估算潮濕外氣的除濕負荷。 Estimate moisture-removal load from humid outdoor air.

降溫本身不證明除濕。 Lower temperature alone does not establish dehumidification.

顯熱與潛熱 Sensible and Latent Heat

滲風 infiltration
新風 outdoor air
太陽得熱 solar heat gain
圍護結構 building envelope
得熱 heat gain
除濕 dehumidification
熱傳導 heat conduction
熱傳率 heat transfer rate
傳熱係數 U-factor

每單位面積和溫差的構造熱傳能力。 Assembly heat transfer per unit area and temperature difference.

U = 1/Rtotal

核對外牆、屋頂及玻璃傳熱。 Check conduction through walls, roofs and glazing.

材料導熱係數 k 與構造 U 的量綱不同。 Material conductivity k and assembly U have different dimensions.

熱傳導 Heat Conduction

熱阻 thermal resistance

阻礙熱流的量,層狀構造常用面積熱阻。 Resistance to heat flow, often reported per area for layers.

R = d/k

在一維串聯近似加總各層及表面熱阻。 Add layers and surface films in a one-dimensional series estimate.

熱橋需要額外核對。 Thermal bridges need a separate check.

隔熱材料 Thermal Insulation

導熱係數 thermal conductivity

描述材料如何傳導熱量的物性。 Material property that describes heat conduction.

k = d/R

比較同厚度材料的隔熱表現。 Compare insulation at equal thickness.

須使用對應材料與工況的值。 Use values for the relevant material and condition.

隔熱材料 Thermal Insulation

淨面積 net area
溫差 temperature difference
熱橋 thermal bridge
冷房容量 cooling capacity
瓦特 watt
冷凍噸 ton of refrigeration (TR)

製冷容量單位,約 3.517 kW。 Unit of refrigeration capacity, approximately 3.517 kW.

1 TR = 12,000 BTU/h

比較型錄冷量、kW 與 TR。 Compare rated capacities in kW and TR.

冷量與設備用電功率是兩個欄位。 Cooling output and electric input are different quantities.

單位相消 unit cancellation
英熱單位 British thermal unit (BTU)
體積流量 volumetric flow rate

每秒通過某截面的體積。 Volume passing through a section per unit time.

V̇ = Av

依截面和流量核對風速。 Check duct velocity from area and flow.

與質量流率的換算需密度。 Conversion to mass flow requires density.

流體流動與壓力 Fluid Flow and Pressure

顯熱法 sensible heat method
乾球溫度 dry-bulb temperature
每分鐘立方英尺 cubic feet per minute (CFM)
送風量 supply airflow
濕度 humidity
相對濕度 relative humidity (RH)

同溫下水蒸氣分壓相對飽和壓的比例。 Water-vapor partial pressure divided by saturation pressure at the same temperature.

RH = 100 pᵥ/pₛₐₜ

配合乾球定位焓濕圖狀態。 Locate a psychrometric state with dry-bulb temperature.

兩股氣流混合時不能直接平均 RH。 Do not average RH when mixing airstreams.

露點與結露 Dew Point and Condensation

露點 dew point

定壓冷卻空氣、直到達飽和的溫度。 Temperature at which air reaches saturation on cooling at constant pressure.

pₛₐₜ(Tdew) = pᵥ

比較同側空氣與玻璃表面。 Compare same-side air dew point with a glazing surface.

露點與濕球溫度含義不同。 Dew point and wet-bulb temperature describe different processes.

露點與結露 Dew Point and Condensation

冷凝 condensation
玻璃表面溫度 glass surface temperature
露點餘量 dew-point margin
水蒸氣分壓 water-vapor partial pressure
焓濕圖 psychrometric chart
含濕比 humidity ratio

水蒸氣質量除以乾空氣質量。 Mass of water vapor divided by mass of dry air.

w = 0.621945pᵥ/(p−pᵥ)

混風及計算除濕量。 Mix airstreams and estimate moisture removal.

g/kg 除以 1000 才能代入 kg/kg 公式。 Divide g/kg by 1,000 before a kg/kg calculation.

顯熱與潛熱 Sensible and Latent Heat

焓 enthalpy

濕空氣在指定參照下按乾空氣質量表示的能量性質。 A moist-air energy property on a dry-air mass basis with a stated reference.

h ≈ 1.006T + w(2501 + 1.86T)

用焓差估盤管總冷量。 Use an enthalpy difference to estimate total coil duty.

kJ/kg 不是 kW,需乘質量流率。 kJ/kg is not kW. Multiply by mass flow.

顯熱與潛熱 Sensible and Latent Heat

飽和線 saturation curve
乾空氣 dry air
濕球溫度 wet-bulb temperature
比容 specific volume
質量流率 mass flow rate
冷卻 cooling
加濕 humidification
再熱 reheat
凝結水 condensate
室外風 outdoor air
回風 return air
混合風 mixed air
質量加權 mass weighting
水側熱平衡 water-side heat balance
供水 supply water
回水 return water
定壓比熱 specific heat capacity
盤管 coil
盤管露點 apparatus dew point (ADP)
旁通因子 bypass factor (BF)
屋頂式空調機組 rooftop unit (RTU)
總冷量 total cooling capacity
顯熱能力 sensible capacity
顯熱比 sensible heat ratio (SHR)
容量餘量 capacity margin
工況 operating condition
變風量 variable air volume (VAV)
分區 zone
主管 main duct
支路 branch
變風量末端 VAV terminal
風閥 damper
回授 feedback
靜壓 static pressure
風機轉速 fan speed
送風重設 supply air reset
風機相似律 fan affinity laws

同一設備在相似運轉點下的轉速比例關係。 Speed scaling at dynamically similar points for the same fan.

Q ∝ N, Δp ∝ N², P ∝ N³

估算轉速變化的理想功率效應。 Estimate the ideal power effect of a speed change.

不同效率或管路條件會偏離立方律。 Efficiency and system changes can invalidate the cube-law estimate.

風機與水泵相似律 Fan and Pump Affinity Laws

空氣側經濟運轉 air-side economizer
混風 mixed air
露點限制 dew-point limit
建築壓差 building pressure difference
風壓 wind pressure
煙囪效應 stack effect
外洩 exfiltration
製冷循環 refrigeration cycle
壓縮機 compressor
冷凝器 condenser
膨脹裝置 expansion device
蒸發器 evaporator
離心式冷水機 centrifugal chiller
喘振 surge
壓力比 pressure ratio
壓縮機圖 compressor map
提升幅度 lift
冷卻塔 cooling tower
進風濕球 entering-air wet bulb
溫降 range
逼近度 approach

冷卻塔出水溫度與進塔空氣濕球的差。 Leaving tower water temperature minus entering-air wet-bulb temperature.

Approach = Tout − Twb

判斷冷卻塔接近濕球極限的程度。 Compare how close tower outlet water approaches wet bulb.

與進出水溫降是不同的量。 Approach differs from the water temperature range.

冷卻塔性能 Cooling Tower Performance

補水 makeup water
蒸發 evaporation
排污 blowdown
漂水 drift
濃縮倍數 cycles of concentration
性能係數 coefficient of performance (COP)

冷房時為冷量除以對應輸入功率。 For cooling, cooling output divided by corresponding input power.

COP = Qcool/Pin

同工況比較設備的能源表現。 Compare energy performance at the same operating point.

額定 COP 不能代替所有部分負荷工況。 A rated COP does not represent every part-load condition.

製冷循環 Refrigeration Cycle

部分負荷比 part-load ratio (PLR)
一次側 primary loop
二次側 secondary loop
解耦管 decoupler
旁通流量 bypass flow
冷凍水 chilled water
低溫差 low delta T
旁通 bypass
感測偏差 sensor bias
泵揚程 pump head
壓差 differential pressure
水力功率 hydraulic power
泵效率 pump efficiency
冷凍站 chiller plant
分段 staging
備援 redundancy
切換 changeover
可用冷量 available capacity
全站效率 plant efficiency
供水重設 supply water temperature reset
取捨 trade-off
總功率 total power
需求控制通風 demand-controlled ventilation (DCV)
占用 occupancy
二氧化碳 carbon dioxide (CO₂)
室內外濃度差 indoor–outdoor concentration difference
水側經濟運轉 water-side economizer
換熱器 heat exchanger
負荷端供水 load-side supply water
分區 zoning
送風 supply air
排風 exhaust air
轉移風 transfer air
風管尺寸 duct sizing
風速 air velocity
壓降 pressure drop

沿流路經摩擦或配件造成的壓力差。 A pressure loss across a flow path or fitting.

Δp = f(L/D)ρv²/2

估算等直徑直管的摩擦損失。 Estimate friction loss for a straight constant-diameter duct.

直管公式不包含彎頭等局部損失。 Straight-duct equations exclude fitting losses.

流體流動與壓力 Fluid Flow and Pressure

等摩擦法 equal-friction method
截面積 cross-sectional area
圖面 drawing
模型標註 model annotation
比例 scale
設備編號 equipment ID
風管明細表 duct schedule
送風口 diffuser
聲壓級 sound pressure level
聲功率級 sound power level
聲學標度 acoustic rating scale
開環 open-loop control
閉環 closed-loop control
設定值 setpoint

控制迴路希望維持的目標值。 Target value for a control loop.

e = setpoint − measured

分析控制誤差與設備回饋。 Analyze control error and equipment feedback.

設定值與實測值可能同時不同。 A setpoint is not proof of the measured value.

PID 控制 PID Control

量測值 measured value
致動器 actuator
兩位控制 on/off control
死區 deadband
遲滯 hysteresis
比例積分微分 proportional–integral–derivative (PID)
感測器 sensor
點位表 point list
歸一化 normalization
回饋 feedback
樓宇管理系統 building management system (BMS)
直接數位控制 direct digital control (DDC)
監控層 supervisory layer
現場層 field layer
通訊協定 communication protocol
資料對照 data mapping
縮放倍率 scale factor
偏移量 offset
資料互通 interoperability
空調箱 air handling unit (AHU)
聯鎖 interlock
啟停順序 start/stop sequence
證明回饋 proof feedback
失效狀態 fault state
射程 throw
展開寬度 spread
下落 drop
有人區 occupied zone
終端速度 terminal velocity
混合送風 mixing ventilation
置換送風 displacement ventilation
分層 stratification
垂直溫差 vertical temperature difference
排煙罩 kitchen exhaust hood
捕集與圍堵 capture and containment
熱羽流 thermal plume
側風 cross-draft
示蹤 tracer
補風 makeup air
廚房排風 kitchen exhaust
鄰區壓差 adjacent-zone pressure difference
排風明細表 exhaust schedule
需求控制排風 demand-controlled kitchen ventilation
平均功率 average power
用電量 electric energy use
水盤管 hydronic coil
分流閥 diverting valve
閥位 valve position
熱源 heat source
局部風速 local air speed
熱舒適 thermal comfort
直吹 draft
參賽論文 competition design narrative
圖說 figure caption
設計取捨 design trade-off
引用 reference
附錄 appendix
計算附錄 calculation appendix
獨立驗算 independent check
殘差 residual

模型值或驗算值減去觀測或原始值的差。 Model or independent-check value minus the observation or baseline.

r = calc − observed

比較模型與獨立量測。 Compare predictions with independent measurements.

正負號及單位需要保留。 Keep the sign and original unit.

有效數字 significant figures
要求追溯矩陣 requirements traceability matrix (RTM)
覆蓋率 coverage
驗收 acceptance
模擬評審 mock review
能耗模型 energy model
能效輸入比 energy input ratio (EIR)
時段能耗 interval energy use
模型驗證 model validation
靈敏度 sensitivity
模擬值 simulated value
趨勢記錄 trend log
警報 alarm
資料品質 data quality
取樣間隔 sampling interval
功能查驗 functional testing
容許差 tolerance
絕對誤差 absolute error
複測 retest
節能驗證 energy savings verification
基準期 baseline period
比較期 reporting period
服務條件 service conditions